26. POTHEADS AND STRESSCONES
26.1 General
Potheads and stresscones provide mechanical support and electrical insulation for
conductors like cable. Insulating capability of these devices is important to prevent a
fault and resulting forced outage.
26.2 Maintenance Schedule for Potheads and Stresscones
Maintenance or Test
Recommended Interval
Reference
Visual inspection for leaks,
cracks
Annually
NFPA 70B, 8-2.4 and
Appendix H
Doble AC loss measurement
(hot collar)
3-6 years
FIST Volume 3-1
Doble Reference Book on
Cables and Accessories
Infrared scan
Annually
NFPA 70B, 18-17
27. REGULATOR, VOLTAGE
27.1 General
Voltage regulators are static devices operating at power system voltages and
frequencies to maintain stable voltage. De-energization is required for some
maintenance. (For excitation system type voltage regulators, see section 16 on
exciters, earlier in this volume).
27.2
Maintenance Schedule for Voltage Regulators
Maintenance or Test
Recommended Interval
Reference
Doble power factor
5 years
Doble Power Factor Test
Data Reference Book
Infrared scan
Annually
NFPA 70B, 18-17
28. RELAYS AND PROTECTION CIRCUITS
28.1 General
Protective relays monitor critical electrical and mechanical quantities and
initiate emergency shutdown whenever they detect out-of-limits conditions.