36
    
    Maintenance or Test
    Recommended Interval
    Reference
    Review equipment ratings
    5 years
    NERC Planning Standard
    Infrared scan
    Annually
    NFPA 70B, 18-17
    Power factor test if oil-filled
    3-6 years
    FIST Volume 3-30
    Dissolved gas analysis if
oil-filled
    Annually
    Reclamation
Recommended Practice
    
    
    Instrument transformers convert power-system level voltages and current to
levels safe to feed meters and other low voltage and current devices. Voltage or
potential transformers generally have output in the 240/120-Vac range, while
current transformers have output in the 2.5- to 5-ampere range. Voltage
transformers may be integral to other equipment or stand-alone. Typically,
current transformers are integral to other equipment (circuit breakers,
transformers) but occasionally may be stand-alone (e.g., 500-kV switchyard at
Grand Coulee).
    Over the course of time, instrument transformers (particularly current
transformers) may become overburdened with the addition of more devices in the
secondary circuit. This may lead to saturation during a fault which may cause the
relay to misoperate. Periodically measuring secondary burden and comparing it to
the transformer rating will indicate if this is a problem.
    Instrument transformer secondary wiring should always be checked for integrity
after any work that may have disrupted these circuits.
    
    Maintenance or Test
    Recommended Interval
    Reference
    Review equipment ratings
    5 years
    NERC Planning Standard
    Burden measurements
    5 years
    FIST Volume 3-8
    Power factor test
    5 years
    Reclamation
Recommended Practice
    Visual inspection
    Annually
    Reclamation
Recommended Practice
    Infrared scan
    Annually
    NFPA 70B, 18-17