39
    Continued
    Heat exchangers - inspect
    Annually
    Transformer FIST
Volume 3-30
    Conservator and bladder -
inspect
    3-5 years
    Transformer FIST
Volume 3-30
    Top oil and winding
thermometers
    Annually inspect and infrared
scan
3-5 years calibrate
    Transformer FIST
Volume 3-30
    Oil level indicator operation
    3-5 years
    Transformer FIST
Volume 3-30
    Pressure relief device
    Annually inspect and perform
function test
3-5 years check oil leaks
    Transformer FIST
Volume 3-30
    Sudden pressure relay
    Annually inspect and perform
function test
3-5 years test per
manufacturer's
recommendations
    Manufacturer's Instructions
Transformer FIST
Volume 3-30
    Buchholz relay
    Annually inspect and perform
function test
    Manufacturer's Instructions
    Tap changer maintenance
    Annually
    Transformer FIST
Volume 3-30
    Deluge system operational
test
    Annually Transformer
    FIST
    Volume 3-30
PO&M 19
    Inspect foundation, rails,
trucks
    3-5 years
    Transformer FIST
Volume 3-30
PO&M 19
    
    
    Transmission lines carry electrical power between the facility and the power system.
Reclamation maintains relatively few transmission lines. However, inspection of
transmission line segments entering switchyards is recommended.