30
The following should be monitored and recorded by a strip chart recorder during a
load rejection test:
Breaker position.-
A reference signal to determine exactly when the breaker opens
can be helpful. This can be a signal from the generator current transformer or a
breaker contact that opens or closes with the main breaker.
Gate position.-
A string transducer or other position transducer should be
connected to one of the servomotors to monitor wicket gate position. The strip
chart recorder should be calibrated from 100- to 0-percent gate.
Unit speed.-
Unit speed should be recorded with a tachometer or frequency
transducer with sufficient range to measure the speed from zero to the predicted
maximum speed.
Spiral case pressure.-
Spiral case pressure should be monitored by a pressure
transducer connected to a valved tap in the spiral case mandoor. If a tap is not
available in the mandoor, the transducer can be installed directly on the
piezometer ring just upstream from the penstock. Installation on a long line or a
line with a bourdon tube type gauge or sensor can lead to false data.
Surge tank pressure.-
A pressure transducer should be mounted at the base of
the surge tank to monitor water elevation in the tank. Under no circumstances
should the water overtop the tank.
Generator voltage.-
A voltage transducer connected to the generator potential
transformer should be used to monitor generator voltage.
Pressure regulator.-
If a pressure regulator or automatic bypass valve is present,
its position should be monitored by a string transducer or other position
transducers.
Shaft runout.-
Proximity probes should be installed at each of the guide bearing
elevations to monitor shaft runout during the load rejection tests.
After the test, the following data should be recorded:
·
Wicket gate timing
·
Maximum shaft speed
·
Maximum spiral case pressure
·
Maximum generator voltage
·
Maximum surge tank pressure or elevation
·
Regulator valve closure time