31
Rev.
12/31/97
TABLE 3. - VALVE REGULATED LEAD-ACID BATTERY (GEL CELL)
MAINTENANCE SCHEDULE
Maintenance
New Battery
Shift
Monthly
3-Month
6-Month
Annual
Visual
Inspection
See 5.6
General
Inspection
Battery Float
Voltage
See 5.7
Panel Meter
Float
Voltage
Battery Float Voltage
with Digital Voltmeter
Cell Float
Voltage
See 5.7
All Cells
with Digital
Voltmeter
Pilot Cells
with Digital
Voltmeter
All Cells
with Digital
Voltmeter
Temperature
Readings
See 5.8
All
Cells
All
Cells
Connection
Resistance
See 5.9
All
Connections
25 Percent
of All
Connections
All
Connections
Internal
Resistance
See 5.10
All
Cells
All
Cells
Battery
Testing
See 5.11
Acceptance
Capacity
Testing
Capacity Test 6
months if 1-year
test <90 percent
Safety
Equipment
See 5.6 & 8.0
Wash Equipment
Protective Clothing
Fire Extinguisher, etc.
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance