EZ Maintenance CMMS Software Img



background image
34
Rev.12/31/97
A. Monthly
A. Monthly
Check for general cleanliness of the battery, mounting rack, and battery
room. Check for electrolyte leaks and cover integrity, and take corrective
action if needed. Check for corrosion at terminals, connectors, racks, and
cabinets. Check the ambient temperature and make sure all ventilation
equipment (fans, vents, etc.) is operable.
Check for availability and condition of all safety equipment, gloves, aprons,
face shields, etc. Check for a full gallon of labeled neutralizing solution.
Check for cleanliness and operability of eyewash station or portable eyewash
equipment and body wash station (see section 8.2). Check for a class C fire
extinguisher and ensure that it has been inspected and tested according to
schedule. Carbon dioxide (CO
2
) fire extinguishers are not recommended
because of the cooling effect they will have on the battery. Check for
availability of insulated tools and utensils so short circuits can be avoided.
5.7 VOLTAGE READINGS
5.7 VOLTAGE READINGS
An accurate digital voltmeter is critical for extended life of the battery (see
section 1.3). At a constant float voltage, the charging current will increase
as the temperature of the electrolyte increases. Therefore, cells of higher
temperature will indicate a lower cell voltage. See figure 10 for proper
meter probe placement. Place the probes across the posts of the cell so as
not to include the voltage drops across the intercell connections.
A. Initial Voltage
A. Initial Voltage
Readings of all cells should be taken and recorded about 24 hours after
placing the battery in float. Select the cell/module with the lowest float
voltage as the pilot cell for future readings. Use form POM-133B for all
voltage readings.
B. Each Shift
B. Each Shift
Check the voltmeter on the charger and adjust the float voltage if necessary.
C. When Taps Are Changed
C. When Taps Are Changed
When taps are changed on the power or station service transformers, check
the float voltage on the charger panel and adjust if necessary.
D. Monthly
D. Monthly
Check and record the voltage of the pilot cell with an accurate digital
voltmeter.
E. Monthly
E. Monthly
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance