EZ Maintenance CMMS Software Img



background image
43
Rev.12/31/97
D. Monthly
D. Monthly
Check the accuracy of the panel voltmeter against the digital voltmeter by
measuring the battery terminal voltage. Adjust the panel voltmeter if
necessary.
E. Quarterly
E. Quarterly
Read the pilot cell voltage and the overall battery terminal voltage while on
float. Read the voltages with the digital voltmeter and record them on form
POM-133C.
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance

This Information is Reprinted From UNITED STATES DEPARTMENT OF THE INTERIOR BUREAU OF RECLAMATION