EZ Maintenance CMMS Software Img



background image
49
Rev.12/31/97
Never approach any storage battery with an
open
flame. The gas given off by
all storage batteries on charge is an explosive mixture of hydrogen and
oxygen..
6.15 BATTERY RECORDS
6.15 BATTERY RECORDS
A manufacturer's warranty provided with each battery extends from the date
of purchase. Battery records are kept to show the care provided during the
service period as well as to facilitate routine battery maintenance. Monthly
report form POM-133C should be filled out each month for each battery and
filed for future reference.
6.16 WALL CARD RECORDS
6.16 WALL CARD RECORDS
To facilitate proper battery operation, maintenance, and care, post a battery
data card (POM-159) in a conspicuous place near the battery to provide the
attendant with service information and data.
7. BATTERIES FOR MICROWAVE AND VHF RADIO EQUIPMENT
7.1 LEAD-ACID BATTERIES
7.1 LEAD-ACID BATTERIES
See section 1 for detailed information.
A. Engine-Generator Starting Batteries
A. Engine-Generator Starting Batteries
Keep the engine-generator starting batteries clean and installed in the trays
provided. The cell tops should be wiped with a solution of 1 pound of
bicarbonate of soda to 1 gallon of water two or three times a year.
Keep the electrical connections tight and free of corrosion. A coating of no-
oxide anti-corrosive grease on terminals will usually prevent corrosion. Dry
sand should be kept in trays on which batteries are placed.
Adjust the charge rate to keep batteries fully charged. Open-cell voltage
should be maintained at the manufacturer's recommended level. Open
circuit voltage on a 12-volt battery should be approximately 12.9 to 13.2
volts d.c., based on the manufacturer's data. Care should be taken not to
overcharge the battery in order to avoid the excessive use of water. Use only
distilled water
When replacing starting batteries, use batteries of equal or greater capacity
than originally installed. The battery should be of sufficient capacity to hold
starting voltage after 30 seconds cranking (10.5 volts d.c. or higher on 12-
volt systems).
If the difference in specific gravity between the highest and lowest cell is
0.050 (50 points) or more, the battery is nearing the end of its useful life
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance

This Information is Reprinted From UNITED STATES DEPARTMENT OF THE INTERIOR BUREAU OF RECLAMATION